InteliLite4 AMF20 Global Guide
477
LBO: F
Related FW 1.3.0 Related applications AMF,MRS
Comm object 592
Description
This output provides 1s pulse when:
Fault Reset button is pressed on the controller front facia or
Fault Reset button is pressed on any of external local/remote terminals or
Fault Reset command is received via communication line or
The input FAULT RESET BUTTON (PAGE 448) is activated.
FltRes Button Echo
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 2695
Description
LBO is active as long as it's button is pressed or it's LBI is active.
FltRes Button State
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1815
Description
The Frequency select output is active when Nominal Frequency (Frequency Settings) is equal to 50Hz
and is deactivated when Nominal Frequency (Frequency Settings) is equal to 60Hz.
Frequency Select
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1253
Description
Output is activated when the value of Fuel Level lies under the value of setpoint Fuel Pump On (page
250) and is deactivated when value of Fuel Pump Off (page 251) is reached.
This output also can be activated by binary input FUEL PUMP ON/OFF (PAGE 449). In this case the binary
output is active until the binary input FUEL PUMP ON/OFF (PAGE 449) is active or until the value of Fuel
Level reaches 100% or the time set by setpoint Transfer Wrn Delay (page 252) elapsed.
Fuel Pump
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 22
Description
Fuel Solenoid