Troubleshooting SiUS041111
94 Service Diagnosis
4.13 Four-Way Valve Abnormality
Remote
Controller
Display
EA
Method of
Malfunction
Detection
The room temperature thermistor, the indoor heat exchanger thermistor, the outdoor temperature
thermistor, and the outdoor heat exchanger thermistor are checked if they function within their
normal ranges in each operation mode.
Malfunction
Decision
Conditions
A following condition continues over 10 minutes after operating for 5 minutes.
Cooling / Dry
(room thermistor temp. – indoor heat exchanger temp.) < –5°C (–9°F)
Heating
(indoor heat exchanger temp. – room thermistor temp.) < –5°C (–9°F)
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four-way valve coil
Defective four-way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve

Table of Contents

Other manuals for Daikin FTXN24KVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXN24KVJU and is the answer not in the manual?

Daikin FTXN24KVJU Specifications

General IconGeneral
BrandDaikin
ModelFTXN24KVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals