Troubleshooting SiUS041111
80 Service Diagnosis
4.3 Freeze-up Protection Control or Heating Peak-cut Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Malfunction
Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 65°C (149°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB

Table of Contents

Other manuals for Daikin FTXN24KVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXN24KVJU and is the answer not in the manual?

Daikin FTXN24KVJU Specifications

General IconGeneral
BrandDaikin
ModelFTXN24KVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals