6-02 Fire Mode Live Zero Timeout Function
Option: Function:
Select the timeout function when
re mode is active. The function set
in this parameter is activated if the
input signal on analog inputs is
lower than 50% of the low value for
a time period dened in
parameter 6-00 Live Zero Timeout
Time.
[0] * Oîš„
[1] Freeze output Frozen at the present value.
[2] Stop Overruled to stop.
[3] Jogging Overruled to jog speed.
[4] Max. speed Overruled to maximum speed.
3.8.2 6-1* Analog Input 1
Parameters for conguring the scaling and limits for analog
input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range: Function:
0.07 V* [ 0 - par. 6-11
V]
NOTICE
For the live zero alarms to
work, parameter 6-10 Terminal
53 Low Voltage must have a
value of 1 V or greater.
Enter the low voltage value. This
analog input scaling value should
correspond to the low reference
feedback value set in
parameter 6-14 Terminal 53 Low Ref./
Feedb. Value.
6-11 Terminal 53 High Voltage
Range: Function:
10 V* [ par. 6-10 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Range: Function:
4 mA* [ 0 - par. 6-13
mA]
Enter the low current value. This
reference signal should correspond
to the low reference feedback value
set in parameter 6-14 Terminal 53
Low Ref./Feedb. Value. Set the value
6-12 Terminal 53 Low Current
Range: Function:
at >2 mA to activate the live zero
timeout function in
parameter 6-01 Live Zero Timeout
Function.
6-13 Terminal 53 High Current
Range: Function:
20 mA* [ par. 6-12 -
20 mA]
Enter the high current value
corresponding to the high
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range: Function:
Size
related*
[-999999.999
- 999999.999 ]
Enter the analog input scaling value
that corresponds to the low
voltage/low current set in
parameter 6-10 Terminal 53 Low
Voltage and parameter 6-12 Terminal
53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Range: Function:
Size
related*
[-999999.999
- 999999.999 ]
Enter the analog input scaling value
that corresponds to the high
voltage/high current value set in
parameter 6-11 Terminal 53 High
Voltage and parameter 6-13 Terminal
53 High Current.
6-16 Terminal 53 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal 53. A
high value improves dampening
but also increases the delay
through the lter.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 107
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals