16-63 Terminal 54 Switch Setting
View the setting of input terminal 54.
Option: Function:
[0] * Current
[1] Voltage
16-64 Analog Input 54
Range: Function:
0* [-20 - 20 ] View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range: Function:
0* [0 - 30 ] View the actual value at output 42
in mA. The value shown reects the
selection in parameter 6-50 Terminal
42 Output.
16-66 Digital Output [bin]
Range: Function:
0* [0 - 15 ] View the binary value of all digital
outputs.
16-67 Pulse Input #29 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual frequency rate on
terminal 29.
16-68 Pulse Input #33 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual value of the
frequency applied at terminal 33 as
an impulse input.
16-69 Pulse Output #27 [Hz]
Range: Function:
0* [0 - 40000 ] View the actual value of impulses
applied to terminal 27 in digital
output mode.
16-70 Pulse Output #29 [Hz]
Range: Function:
0* [0 - 40000 ] View the actual value of pulses to
terminal 29 in digital output mode.
16-71 Relay Output [bin]
Range: Function:
0* [0 - 511 ] View the settings of all relays.
16-71 Relay Output [bin]
Range: Function:
Illustration 3.52 Relay Settings
16-72 Counter A
Range: Function:
0* [-2147483648
-
2147483647 ]
View the present value of counter
A. Counters are useful as
comparator operands, see
parameter 13-10 Comparator
Operand.
Reset or change the value either via
digital inputs (parameter group 5-1*
Digital Inputs) or by using an SLC
action (parameter 13-52 SL Controller
Action).
16-73 Counter B
Range: Function:
0* [-2147483648
-
2147483647 ]
View the present value of counter
B. Counters are useful as
comparator operands,
parameter 13-10 Comparator
Operand.
Reset or change the value either via
digital inputs (parameter group 5-1*
Digital Inputs) or by using an SLC
action (parameter 13-52 SL Controller
Action).
16-75 Analog In X30/11
Range: Function:
0* [-20 - 20 ] View the actual value at input
X30/11 of VLT
®
General Purpose I/O
MCB 101.
16-76 Analog In X30/12
Range: Function:
0* [-20 - 20 ] View the actual value at input
X30/12 of VLT
®
General Purpose I/O
MCB 101.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
168 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals