3-11 Jog Speed [Hz]
Range: Function:
Size
related*
[ 0 - par. 4-14
Hz]
The jog speed is a xed output
speed at which the frequency
converter is running when the jog
function is activated.
See also parameter 3-19 Jog Speed
[RPM] and parameter 3-80 Jog Ramp
Time.
3-13 Reference Site
Option: Function:
Select which reference site to
activate.
[0] * Linked to
Hand / Auto
Use local reference when in hand-
on mode, or remote reference
when in auto-on mode.
[1] Remote Use remote reference in both hand-
on mode and auto-on mode.
[2] Local Use local reference in both hand-on
mode and auto-on mode.
NOTICE
When set to [2] Local, the
frequency converter starts with
this setting again after a
power-down.
[3] Linked to H/A
MCO
Select this option to enable the
FFACC factor in
parameter 32-66 Acceleration Feed-
Forward. Enabling FFACC reduces
jitter and makes the transmission
from the motion controller to the
control card of the frequency
converter faster. This leads to faster
response times for dynamic
applications and position control.
For more information about FFACC,
see VLT
®
Motion Control MCO 305
Operating Instructions.
3-14 Preset Relative Reference
Range: Function:
0 %* [-100 -
100 %]
The actual reference, X, is increased
or decreased with the percentage Y,
set in parameter 3-14 Preset Relative
Reference.
This results in the actual reference
Z. Actual reference (X) is the sum of
the inputs selected in:
3-14 Preset Relative Reference
Range: Function:
•
Parameter 3-15 Reference 1
Source.
•
Parameter 3-16 Reference 2
Source.
•
Parameter 3-17 Reference 3
Source.
•
Parameter 8-02 Control
Source.
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
130BA059.12
Z
Illustration 3.19 Preset Relative Reference
X
100
%
0-100
Z
Y
X+X*Y/100
P 3-14
130BA278.10
Illustration 3.20 Actual Reference
3-15 Reference 1 Source
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select the reference input to be
used for the 1
st
reference signal:
•
Parameter 3-15 Reference 1
Source.
•
Parameter 3-16 Reference 2
Source.
•
Parameter 3-17 Reference 3
Source.
Dene up to 3 dierent reference
signals. The sum of these reference
signals denes the actual reference.
[0] No function
[1] * Analog Input
53
Parameter Descriptions
VLT
®
HVAC Drive FC 102
76 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals