4.6.1 Wiring AS324MT-A
Input form
X0.0+ to X0.3+/X0.0- to X0.3- : Differential input
X0.4–X0.11: Direct current (sinking or sourcing)
Input current/voltage
X0.0+ to X0.3+/X0.0- to X0.3- : 5V DC, 5 mA
X0.4–X0.11: 24 VDC, 5 mA
Output form
Y0.0+ to Y0.3+/Y0.0- to Y0.3- : Differential input
Y0.4–Y0.11: Transistor-T (sinking)
Output current/voltage
Y0.0+ to Y0.3+/Y0.0- to Y0.3-: 5V DC, 20mA/output
(+ and – as a group, e.g. Y0.0+ and Y0.0- is a group)
Y0.4 to Y0.11: 5 to 30V DC, 0.1A/output, 0.8A/COM
COM1
COM2
5
0
OUT
4
1
2
3
8
9
11
10
2
102
7
5
6
4
IN
3 11
AS324MT
0
1
8
9
40
1
BAT. LO W
ERROR
RUN
POWER
Ethernet
6
7