0044
Connection lost in the mode of
current input 4 mA - 20 mA for the
function card 1 (AS-F2AD) or for
the built-in AD input channel 1.
Check the connection cable.
SM27 H
0045
Connection lost in the mode of
current input 4 mA - 20 mA for the
function card 1 (AS-F2AD) or for
the built-in AD input channel 2.
Check the connection cable. SM27 H
0046
Connection lost in the mode of
current input 4 mA - 20 mA for the
input channel 1 of the function
card 2 (AS-F2AD).
Check the connection cable. SM27 H
0047
Connection lost in the mode of
current input 4 mA - 20 mA for the
input channel 2 of the function
card 2 (AS-F2AD).
Check the connection cable. SM27 H
1500
Connection lost in the remote
modules
Check the network connection cable. SM30 V
1502
-
150F
Errors occurred in the remote
modules
Refer to Section 12.3.7 for more information on the
remote module error codes.
SM30 V
1800
-
180F
Errors occurred in the extension
modules
Refer to Section 12.3 for more information on the
extension module error codes.
SM10 V
1900
-
191C
Heartbeat errors occurred in the
slave in CANopen / ECAT
communication.
1. Check the CANopen / ECAT connection cable.
2. Check if the specific slave is working properly.
Note: The last 2 digits of the error code represe
nt the ID
number of the slave (convert hexadecimal to decimal).
- V
12.2.5
BAT. LOW LED Indicators Are ON
The blinking happens when there is no battery (CR1620) or the power is low. Turn this option off in the HWCONFIG >
CPU > Device Setting > Show Battery Low Voltage Error CPU when you dont need the RTC function to keep track of the
current time (default is enabled).
Error
Code
(16#)
Description Solution Flag Log
0027 Battery Low Change battery or turn this option off SM219
X
12.2.6
BAT. LOW LED Indicators Blinking Every 0.5 Seconds
The blinking happens when RTC cannot keep track of the current time.
Error
Code
(16#)
Description Solution Flag Log
0026
RTC cannot keep track of the
current time
If the problem persists, contact the local authorized
distributors.
SM218
V
0028 No response from RTC
If the problem persists, contact the local authorized
distributors.
SM217
V
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS218TX-A and is the answer not in the manual?

Delta AS218TX-A Specifications

General IconGeneral
BrandDelta
ModelAS218TX-A
CategoryControl Unit
LanguageEnglish

Related product manuals