12.2.7
The LED RUN and ERROR Indicators are Blinking
Simultaneously Every 0.5 Seconds
The blinking happens when the firmware of the CPU module is being upgraded. If this happens once the power is
supplied to the CPU module, it means errors occurred during the previous firmware upgrade. Users need to upgrade the
firmware again or contact your point of purchase.
12.2.8
The RUN and ERROR LED Indicators are Blinking One After
Another Every 0.5 Seconds.
The blinking happens when the CPU module memory card is backing up, restoring, or saving.
If you are using AS218 Series CPU and without engaging any SD card, the RUN and LED indicators blinking indicates
the AIO firmware is being updated. If the blinking happens at the instant when the CPU is supplied with power, the
blinking means AIO firmware update failed and you need to update the firmware again. If you are not updating the AIO
firmware, the blinking indicates CPU error and you need to contact the local authorized distributors.
12.2.9
Other Errors (Without LED Indicators)
Error
Code
(16#)
Description Solution Flag Log
0011
The PLC ID is incorrect.
Check the PLC ID.
SM34
V
0012
The PLC password is incorrect.
Check the PLC password.
SM34
V
002D
The PLC maximum password attempts
exceeded.
Reset the CPU module or restore the CPU module
to its default settings.
SM34 V
0050
The memories in the latched special
auxiliary relays are abnormal.
1. Reset the CPU module or restore the CPU
module to its default settings, and then download
the program and the parameters again.
2. If the problem persists, contact the local
authorized distributors.
SM6 V
0051
The latched special data registers are
abnormal.
1. Reset the CPU module or restore the CPU
module to its default settings, and then download
the program and the parameters again.
2. If the problem persists, contact the local
authorized distributors.
SM6 V
0052
The memories in the latched auxiliary
relays are abnormal.
1. Reset the CPU module or restore the CPU
module to its default settings, and then download
the program and the parameters again.
2. If the problem persists, contact the local
authorized distributors.
SM6 V
0054 The latched counters are abnormal.
1. Reset the CPU module or restore the CPU
module to its default settings, and then download
the program and the parameters again.
2. If the problem persists, contact the local
authorized distributors.
SM6 V
0055
The latched 32-bit counters are
abnormal.
1. Reset the CPU module or restore the CPU
module to its default settings, and then download
the program and the parameters again.
2. If the problem persists, contact the local
authorized distributors.
SM6 V
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS218TX-A and is the answer not in the manual?

Delta AS218TX-A Specifications

General IconGeneral
BrandDelta
ModelAS218TX-A
CategoryControl Unit
LanguageEnglish

Related product manuals