To prevent an unexpected shock from resulting in damage to the AS Series system and a
controlled element, ensure that the modules are correctly and firmly installed.
D.2 Daily Maintenance
To keep an AS series system operating normally, ensure that the ambient environment and the AS series system
conform to the cautions listed in section D.1. You can then perform the daily inspection described below. If you find any
problems, follow the solution and perform any necessary maintenance.
D.2.1 Required Inspection Tools
A screwdriver
Industrial alcohol
A clean cotton cloth
D.2.2 Daily Inspection
No. Item Inspection Criterion Remedy
1 Appearance Check visually.
Dirt must not be
present.
Remove the dirt.
2 Installing of a backplane
Check whether the set
screws are loose.
The backplane must
be installed firmly.
Tighten the
screws.
Check whether the
backplane is installed on
the DIN rail properly.
Install the
backplane on the
DIN rail properly.
3 Installing of a module
Check whether the
module is loose that the
projection is inserted into
the hole on the backplane,
and that the screw is
tightened.
The projection under
the module must be
inserted into the hole
in the backplane, and
the screw must be
tightened.
Install the module
firmly.
4 Connection
Check whether the
removable terminal block
is loose.
The removable
terminal block must
not be loose.
Install the terminal
block firmly.
Check whether the
connector is loose.
The connector must
not be loose.
Tighten the
screws on the
connector.