Conducted immunity test
Environmental phenomenon
Fast transient
burst
High energy surge
Radio frequency
interference
Reference standard IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6
Interface/Port
Specific
interface/port
Test level Test level Test level
Data
communication
Shielded cable 1 kV 1 kV CM 10 V
Unshielded cable 1 kV 1 kV CM 10 V
Digital and analog
I/O
AC I/O
(unshielded)
2 kV
2 kV CM
1 kV DM
10 V
Analog or DC
I/O(unshielded)
1 kV 1 kV CM 10 V
All shielded lines
(to the earth)
1 kV 1 kV CM 10 V
Equipment power
AC power 2 kV
2 kV CM
1 kV DM
10 V
DC power 2 kV
0.5 kV CM
0.5 kV DM
10 V
I/O power and
auxiliary power
output
AC I/O and AC
auxiliary power
2 kV
2 kV CM
1 kV DM
10 V
DC I/O and DC
auxiliary power
2 kV
0.5 kV CM
0.5 kV DM
10 V