Chapter 8 Option CardsC2000
8-38
8-15 CMC-EC01 -- Communication card, EtherCAT
8-15-1 Features
The EtherCAT of C2000 currently provides standard control mode of CiA402 Velocity (Index
6060=2), but it is non-synchronous control mode. There is no need to turn on the DC (Distribute
Clock) function when operating. However, if the DC function is required for using with synchronous
products (e.g. ASDA-A2), the CMC-EC01 can still be used normally under this circumstances. The
VFD-C2000 supports the EtherCAT function with firmware version 2.02 and above. Please be
attention to the firmware you use.
8-15-2 Product Profile
[Figure 1]
1. Screw fixing hole
2. Positioning hole
3. RUN indicator
4. ERR indicator
5. POWER indicator
6. OUT LINK indicator
7. IN LINK indicator
8. Fool-proof groove
9. RJ-45 connection port
10. RJ-45 connection port
11. Control board connection port
8-15-3 Specifications
Network Interface
Interface RJ-45
Number of ports 2 Port
Transmission method IEEE802.3, IEEE802.3u
Transmission cable Category 5e shielding 100 M
Transmission speed 10 / 100 Mbps Auto-Defect
Network protocol EtherCAT
Electrical Specification
Power supply voltage 5V
DC
Power consumption 0.8W
Insulation voltage 500V
DC
Weight (g) 27

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals