Chapter 15 CANopen Overview C2000
15-7
15-3 CANopen Communication Interface Descriptions
15-3-1 CANopen Control Mode Selection
There are two control modes for CANopen: the DS402 standard (Pr. 09-40 set to 1) is the default,
and the Delta’s standard setting (Pr. 09-40 set to 0). There are two control modes according to
Delta’s standard. One is the old control mode (Pr. 09-30 = 0); this control mode can only control the
motor drive under frequency control. The other mode is a new standard (Pr. 09-30 = 1); this new
control mode allows the motor drive to be controlled under multiple modes. The C2000 currently
supports speed, torque, position and home mode. The following table shows the control mode
definitions:
CANopen
Control
Mode
Selection
Control Mode
Speed Torque Position Home
Index Description Index Description Index Description Index Description
DS402
standard
Pr. 09-40=1
6042-00
Target
Rotating
Speed (RPM)
6071-00
Target Torque
(%)
607A-00
Target
Position
----- -----
----- ----- 6072-00
Max. Torque
Limit (%)
----- ----- ----- -----
Delta Standard
(Old definition)
Pr. 09-40=1,
Pr. 09-30=0
2020-02
Target
Rotating
Speed (Hz)
----- ----- ----- ----- ----- -----
Delta Standard
(New definition)
Pr. 09-40=0,
Pr. 09-30=1
2060-03
Target
Rotating
Speed (Hz)
2060-07
Target Torque
(%)
2060-05
Target
Position
----- -----
2060-04
Torque Limit
(%)
2060-08 Speed Limit (Hz) ----- ----- ----- -----
CANopen Control Mode
Selection
Operation Control
Index Description
DS402 standard
Pr. 09-40=1
6040-00 Operation Command
----- -----
Delta Standard (Old definition)
Pr. 09-40=1, Pr. 09-30=0
2020-01 Operation Command
Delta Standard (New definition)
Pr. 09-40=0, Pr. 09-30=1
2060-01 Operation Command
----- -----
CANopen Control Mode
Selection
Other
Index Description
DS402 standard
Pr. 09-40=1
605A-00 Quick stop processing mode
605C-00 Disable operation processing mode
Delta Standard (Old definition)
Pr. 09-40=1, Pr. 09-30=0
----- -----
Delta Standard (New definition)
Pr. 09-40=0, Pr. 09-30=1
----- -----
----- -----
You can use some indices in either DS402 or Delta’s standard.
For example:
1. Indices that are defined as RO attributes.
2. The corresponding index of available parameter groups: (2000-00–200B-XX)
3. Accelerating / Decelerating Index: 604F 6050

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals