Chapter 12 Description of Parameter SettingsC2000
12.1-01-1
01 Basic Parameters You can be set this parameter during operation.
Maximum Operation Frequency
Default: 60.00 / 50.00
Settings 00.00–599.00 Hz
Determines the AC motor drive’s maximum operation frequency range. This setting corresponds
to the maximum value for the analog input frequency setting signal (0 – +10 V, 4–20 mA,
0–20 mA, ±10 V).
In normal load mode:
VF, SVC, VFPG, FOCPG: 0–599 Hz
FOC sensorless (IM/PM): 0–300H z/ 500 Hz
In heave load mode:
Output range: 0–300 Hz
Output Frequency of Motor 1base frequency and motor rated frequency
Output Frequency of Motor 2base frequency and motor rated frequency
Default: 60.00 / 50.00
Settings 0.00599.00 Hz
Set the value according to the motors rated frequency from the motor’s nameplate. If the motor’s
rated frequency is 60 Hz, set the value to 60 Hz. If the motors rated frequency is 50 Hz, set the
value to 50 Hz.
Output Voltage of Motor 1base frequency and motor rated frequency
Output Voltage of Motor 2base frequency and motor rated frequency
Default:
200.0 / 400.0 / 575.0 / 660.0
Settings 230V series: 0.0–255.0 V
460V series: 0.0–510.0 V
575V series: 0.0–637.0 V
690V series: 0.0–765.0 V
Set the value according to the motor’s rated voltage from the motor’s nameplate. If the motor’s
rated voltage is 220 V, set the value to 220.0 V. If the motor’s rated voltage is 200 V, set the value
to 200.0 V.
There are a wide variety of motors, but the power system for each country is different. The
convenient and economical way to solve this problem is to use an AC motor drive, which can deal
with different voltages and frequencies, while supporting the original characteristics and life of the
motor.
Mid-point Frequency 1 of Motor 1
Default: 3.00
Settings 0.00599.00 Hz

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals