Chapter 11 Summary of Parameter SettingsC2000
11-10
01 Basic Parameters
Pr. Parameter Name Setting Range Default
01-00 Maximum operation frequency 0.00–599.00 Hz
60.00 /
50.00
01-01 Output frequency of motor 1 0.00–599.00 Hz
60.00 /
50.00
01-02 Output voltage of motor 1
230V: 0.0–255.0 V
460V: 0.0–510.0 V
575V: 0.0–637.0 V
690V: 0.0–765.0 V
200.0
400.0
575.0
660.0
01-03 Mid-point frequency 1 of motor 1 0.00–599.00 Hz 3.00
01-04 Mid-point voltage 1 of motor 1
230V: 0.0–240.0 V
460V: 0.0–480.0 V
575V: 0.0–637.0 V
690V: 0.0–720.0 V
11.0
22.0
0.0
0.0
01-05 Mid-point frequency 2 of motor 1 0.00–599.00 Hz 1.50
01-06 Mid-point voltage 2 of motor 1
230V: 0.0–240.0 V
460V: 0.0–480.0 V
575V: 0.0V–637.0 V
690V: 0.0–720.0 V
5.0
10.0
0.0
0.0
01-07 Min. output frequency of motor 1 0.00–599.00 Hz 0.50
01-08 Min. output voltage of motor 1
230V: 0.0–240.0 V
460V: 0.0–480.0 V
575V: 0.0–637.0 V
690V: 0.0–720.0 V
1.0
2.0
0.0
0.0
01-09 Start-up frequency 0.00–599.00 Hz 0.50
01-10 Output frequency upper limit 0.00–599.00 Hz
599.00
01-11 Output frequency lower limit 0.00–599.00 Hz
0
01-12 Acceleration time 1
Pr. 01-45=0: 0.00–600.00 sec.
Pr. 01-45=1: 0.00–6000.0 sec.
The default of motor drive with 30HP and above:
60.00 / 60.0
10.00
01-13 Deceleration time 1
Pr. 01-45=0: 0.00–600.00 sec.
Pr. 01-45=1: 0.00–6000.0 sec.
The default of motor drive with 30HP and above:
60.00 / 60.0
10.00
01-14 Acceleration time 2
Pr. 01-45=0: 0.00–600.00 sec.
Pr. 01-45=1: 0.00–6000.0 sec.
The default of motor drive with 30HP and above:
60.00 / 60.0
10.00
01-15 Deceleration time 2
Pr. 01-45=0: 0.00–600.00 sec.
10.00