Chapter 11 Summary of Parameter SettingsC2000
11-20
03 Analog Input / Output Parameters
Pr. Parameter Name Setting Range Default
03-00 Analog input selection (AVI) 0: No function 1
03-01 Analog input selection (ACI) 1: Frequency command (speed limit under torque 0
03-02 Analog input selection (AUI) control mode) 0
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC / KTY-84) input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive / negative torque limit
11: PT100 thermistor input value
13: PID compensation value
03-03 Analog input bias (AVI) -100.0–100.0%
0.0
03-04 Analog input bias (ACI) -100.0–100.0% 0.0
03-05 Analog input bias (AUI) -100.0–100.0% 0.0
03-07
Positive / negative bias mode
(AVI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Bias serves as the center
0
03-08
Positive / negative bias mode
(ACI)
03-09
Positive / negative bias mode
(AUI)
03-10
Reverse setting when analog
signal input is negative
frequency
0: Negative frequency is not allowed. The digital
keypad or external terminal controls the forward and
reverse direction.
1: Negative frequency is allowed. Positive frequency =
run in forward direction; negative frequency = run in
reverse direction. The digital keypad or external
terminal control cannot switch the running direction.
0
03-11 Analog input gain (AVI) -500.0–500.0% 100.0
03-12 Analog input gain (ACI) -500.0–500.0% 100.0
03-13 Analog positive input gain (AUI) -500.0–500.0% 100.0
03-14 Analog negative input gain (AUI) -500.0–500.0% 100.0
03-15 Analog input filter time (AVI) 0.00–20.00 sec. 0.01
03-16 Analog input filter time (ACI) 0.00–20.00 sec. 0.01
03-17 Analog input filter time (AUI) 0.00–20.00 sec. 0.01