Chapter 11 Summary of Parameter SettingsC2000
11-37
07 Special Parameters
Pr. Parameter Name Setting Range Default
07-00 Built-in software brake level
230V: 350.0–450.0V
DC
460V: 700.0–900.0V
DC
575V: 850.0–1116.0V
DC
690V: 939.0–1318.0V
DC
370.0
740.0
895.0
1057.0
07-01 DC brake current level 0–100% 0
07-02 DC brake time at run 0.0–60.0 sec. 0.0
07-03 DC brake time at stop 0.0–60.0 sec. 0.0
07-04 DC brake frequency at stop 0.00–599.00Hz 0.00
07-05 Voltage increasing gain 1–200% 100
07-06
Restart after momentary power
loss
0: Stop operation
1: Speed tracking by speed before the power loss
2: Speed tracking by minimum output frequency
0
07-07 Allowed power loss duration 0.0–20.0 sec. 2.0
07-08 Base block time 0.0–5.0 sec. #.#
07-09 Current limit of speed tracking 20–200% 100
07-10 Restart after fault action
0: Stop operation
1: Speed tracking by current speed
2: Speed tracking by minimum output frequency
0
07-11
Number of times of restart after
fault
0–10 0
07-12 Speed tracking during start-up
0: Disable
1: Speed tracking by maximum output frequency
2: Speed tracking by motor frequency at start
3: Speed tracking by minimum output frequency
0
07-13 dEb function selection
0: Disable
1: dEb with auto-acceleration / auto-deceleration, the
drive does not output the frequency after the power is
restored.
2: dEb with auto-acceleration / auto-deceleration, the
drive outputs the frequency after the power is
restored
3: dEb low-voltage control, then increase to 350V
DC
/
700V
DC
and decelerate to stop
4: dEb high-voltage control of 350V
DC
/ 700V
DC
and
decelerate to stop
0
07-14 dEb function reset time
0.0–25.0 sec.
3.0
07-15 Dwell time at acceleration 0.00–600.00 sec. 0.00
07-16 Dwell frequency at acceleration 0.00–599.00Hz 0.00
07-17 Dwell time at deceleration 0.00–600.00 sec. 0.00
07-18 Dwell frequency at deceleration 0.00–599.00Hz 0.00