Chapter 11 Summary of Parameter SettingsC2000
11-28
Pr. Parameter Name Setting Range Default
05-18
Stator resistance (Rs) for
induction motor 2
0.000–65.535
Depending
on the
model
power
05-19
Rotor resistance (Rr) of induction
motor 2
0.000–65.535
0.000
05-20
Magnetizing inductance (Lm) of
induction motor 2
0.0–6553.5mH
0.0
05-21
Stator inductance (Lx) of
induction motor 2
0.0–6553.5mH
0.0
05-22 Induction motor 1 / 2 selection
1: Motor 1
2: Motor 2
1
05-23
Frequency for Y-connection /
ᇞ-connection switch for an
induction motor
0.00–599.00Hz
60.00
05-24
Y-connection /
ᇞ-connection
switch for induction motor
0: Disable
1: Enable
0
05-25
Delay time for Y-connection /
ᇞ-connection switch for an
induction motor
0.000–60.000 sec.
0.200
05-28
Accumulated Watt-hour for a
motor (W-hour)
Read only 0.0
05-29
Accumulated Watt-hour for a
motor in low word (kW-hour)
Read only 0.0
05-30
Accumulated Watt-hour for a
motor in high word (MW-hour)
Read only 0
05-31
Accumulated motor operation
time (Min.)
0–1439 0
05-32
Accumulated motor operation
time (Day)
0–65535 0
05-33
Induction motor (IM) or
permanent magnet motor (PM)
selection
0: IM
1: SPM (Surface permanent magnet motor)
2: IPM (Interior permanent magnet motor)
0
05-34
Full-load current for a permanent
magnet motor
Depending on the model power
Depending
on the
model
power
05-35
Rated power for a permanent
magnet motor
0.00–655.35kW
Depending
on the
model
power
05-36
Rated speed for a permanent
magnet motor
0–65535rpm 2000
05-37
Pole number for a permanent
magnet motor
0–65535 10