Chapter 11 Summary of Parameter SettingsC2000
11-35
Pr. Parameter Name Setting Range Default
06-36 IGBT temperature at malfunction -3276.7–3276.7°C
Read
only
06-37
Capacitance temperature at
malfunction
-3276.7–3276.7°C
Read
only
06-38 Motor speed at malfunction -32767–32767rpm
Read
only
06-39 Torque command at malfunction -32767–32767%
Read
only
06-40
Status of the multi-function input
terminal at malfunction
0000h–FFFFh
Read
only
06-41
Status of the multi-function output
terminal at malfunction
0000h–FFFFh
Read
only
06-42 Drive status at malfunction 0000h–FFFFh
Read
only
06-44 STO latch selection
0: STO latch
1: STO no latch
0
06-45
Treatment to output phase loss
protection (OPHL)
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46
Detection time of output phase
loss
0.000–65.535 sec.
3.000
06-47
Current detection level for output
phase loss
0.00–100.00%
1.00
06-48
DC brake time of output phase
loss
0.000–65.535 sec.
0.000
06-49 LvX auto-reset
0: Disable
1: Enable
0
06-50
Time for input phase loss
detection
0.00–600.00 sec. 0.20
06-51 CAP oH warning level 0.0–110.0 degree
Depending
on the
motor
power
06-52
Ripple of input phase loss
230V series: 0.0–160.0V
DC
460V series: 0.0–320.0V
DC
575V series: 0.0–400.0V
DC
690V series: 0.0–480.0V
DC
30.0
60.0
75.0
90.0
06-53
Detected input phase loss (OrP)
action
0: Warn and ramp to stop
1: Warn and coast to stop
0
06-55 Derating protection
0: Constant rated current and limit carrier wave by
load current and temperature
0