Chapter 13 Warning CodesC2000
13-2
ID No. Display on LCM Keypad Warning Name Description
3
Communication error 3
(CE3)
RS-485 Modbus illegal data value
Action and Reset
Action level When the length of communication data is too long
Action time Immediately act
Warning setting parameter N/A
Reset method
“Warning” occurs when Pr. 09-02=0 and the motor drive keeps running. The
drive resets automatically when receiving the correct communication data value.
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
Incorrect communication
command from upper unit
Check if the communication command is correct.
Malfunction caused by interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
from the upper unit
Check if the setting for Pr. 09-02 is the same as the setting for the upper unit.
Disconnection or bad connection
of the cable
Check the cable and replace it if necessary.
ID No. Display on LCM Keypad Warning Name Description
4
Communication error 4
(CE4)
RS-485 Modbus data is written to read-only address
Action and Reset
Action level When the data is written to read-only address
Action time Immediately act
Warning setting parameter N/A
Reset method
“Warning” occurs when Pr. 09-02=0 and the motor drive keeps running. The
drive resets automatically when receiving the correct written address of
communication data.
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
Incorrect communication
command from upper unit
Check if the communication command is correct.
Malfunction caused by interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
from the upper unit
Check if the setting for Pr. 09-02 is the same as the setting for the upper unit.
Disconnection or bad connection
of the cable
Check the cable and replace it if is necessary.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals