Operating the PV inverter
7.3.6.4 Active/Reactive Power control for Italy CEI 0-21 and Italy A70
Below is an overview of the features that are adjustable to control the production of active and
reactive power for Italy CEI 0-21 and Italy A70. Italy CEI 0-21 is applicable for low voltage grids
and A70 is applicable for medium voltage grids.
Feature Available for Description
CEI 0-21 A70
Active power control
Power limit x x To reduce the maximum power
production
Power vs. frequency x x To set the power gradiant in
dependency of the frequency
Reactive power control
Constant cos φ This feature is not available for
CEI 0-21 and A70.
cos φ (p) x x To set a cos φ (inductive or
capacative) in dependency of
the active power ratio P/P
n
Constant reactive power x x To set the reactive power ratio
Q/S
n
.
Q (V) x x To set the reactive power ratio
Q/S
n
in dependency of the volt-
age V.
Note: User can activate both the Power
Limit and the Power vs. Frequency at the
same time.
For the reactive power control features:
cosφ(P), Constant Reactive Power, and
Q(V) only one of these items can be activa-
ted at a time.
p indicates a function is executing
* This feature is disabled for CEI 0-21 and
A70 although it will appear in the menu
Figure 7.27.: Active/Reactive Power settings page

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta SOLIVIA 10 EU T4 TL and is the answer not in the manual?

Delta SOLIVIA 10 EU T4 TL Specifications

General IconGeneral
BrandDelta
ModelSOLIVIA 10 EU T4 TL
CategoryInverter
LanguageEnglish

Related product manuals