Operating the PV inverter
Reactive Power Control
21. Jun 2010 13:50
Qi limit
Qs limit Ind 15
Cap 60
[
[
]
]
%
%
V2i
207.0[ ]
V
V2s 236[ ]
V
230[ ]
V
V1i
V1s 230[ ]
V
Reactive Power Control
21. Jun 2010 13:50
0[ ]
%
Mode
ClassB[ ]
Class B
[ ]
Class C
[ ]
O
[ ]
Lock-out Power
0[ ]Lock-in Power %
Delay Time
10[ ]
s
a
b
c
d
e
f
Figure 7.40.: Q(V) settings
Adjustable parameters (Class C)
Parameter Adjustable values Description
Qs limit
(Q/Sn)
0 ... 63% Ind 15%
inductive
Qi limit
(Q/Sn)
0 ... 63% Cap 60%
capacitive
V1s 230 ... 264.5 V default 230 V
V2s 230 ... 264.5 V default 236 V (limit 264.5 / V1s < V2s)
V1i 184 ... 230 V default 230 V
V2i 184 ... 230 V default 207 V (V2i < V1i)
Lock-in Power 0 Not applicable
Lock-out Power 0 Not applicable
Delay time 0 ... 120 s 10 s
Mode Class B I Class C I
OFF
This switches between Class B and Class C or
OFF
Note: At the time of the manual printing, SONDO Class C was implemented in the inverter,
but not yet Class B. Please check for Class B setting availability on our web site at
www.solar-inverter.com. We will post the certicate for SONDO Class B when it is available.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta SOLIVIA 10 EU T4 TL and is the answer not in the manual?

Delta SOLIVIA 10 EU T4 TL Specifications

General IconGeneral
BrandDelta
ModelSOLIVIA 10 EU T4 TL
CategoryInverter
LanguageEnglish

Related product manuals