Operating the PV inverter
NOTE
The Power vs Frequency
function is required for
CEI 0-21 and A70. Please
make sure the Mode is
ON and do not turn off.
*Recovery Frequency is dened in the
grid setting parameters 49.9 - 50.1 Hz by
default.
Figure 7.30.: Power vs. Frequency
Adjustable parameters
Parameter Adjustable Values Description
Actual / Rated Power Actual will be default
Start frequency 50 - 55 Hz 50.3 Hz will be the default. This is the fre-
quency when the power reduction starts
Stop frequency Stop frequency means the frequency when
power = 0. This value is calculated by the gra-
dient and the start frequency.
Recovery frequency Nonadjustable
Gradient 2.0 ... 5.0 % 2.4 % is the default
Recovery time 300 seconds
Mode ON | OFF Switches the feature on and off
7.3.6.4.3 
This feature is not available for CEI 0-21 or A70.
7.3.6.4.4
cos
This feature is available for Italy CEI 0-21 and Italy A70.
With this feature a solar inverter can regulate the power factor as a function of the actual delivered
active power.
The following graph is an example how the values could be set:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta SOLIVIA 10 EU T4 TL and is the answer not in the manual?

Delta SOLIVIA 10 EU T4 TL Specifications

General IconGeneral
BrandDelta
ModelSOLIVIA 10 EU T4 TL
CategoryInverter
LanguageEnglish

Related product manuals