6.2.1 Display Alarm Log
At the time the alarm occurs, the alarm is displayed on the bottom line of the
message center. This display lists the last nine alarms that have occurred. The rst
alarm listed is the most recent to occur. The alarm list progresses from the most
recent to the oldest. The following alarms may be displayed.
EFM MONITOR OPEN INHIBIT
OPEN TORQUE_% CLOSE INHIBIT
CLOSE TORQUE_% LOCAL ESD
VALVE STALLED REMOTE ESD
VALVE DRIFT LOST AIN1 SIGNAL
POWER FAIL ACTUATOR FAIL
LOST PHASE SETUP ERROR
MOTOR OVERLOAD SET LIMITS BEFORE OPERATING
NOTE:
When the “SET LIMITS BEFORE OPERATING” alarm is displayed, no other alarms
will be displayed until the limits are set.
1. At the “DISPLAY ALARM LOG?” prompt, answer “YES.”
2. Use the selector knob (NEXT/BACK) to review the alarms. See Figure 6-2.
NOTE:
The control knob (YES/NO) can be used to view the alarms however do
not cycle the control knob between NO and YES because the unit could
display the “SETUP” mode.
3. Use the control knob (NO) to exit the display.
Figure 6-2 Display Alarm Log Example