EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 16 of 90
Timer Settings Icon Indicates which timer setting is active (A,B)
From this page, by pressing the RIGHT or LEFT key you can view other information concerning pumps, fans, compressors, defrost,
circuit state, RTC, and all probes configured. If one of the probes is in error, the value field of the corresponding probe shows “----“, or
“----“ if the probe is disabled.
By pressing the ESC key from this page, the user accesses the Alarms page.
On the two-line display, the top line shows the Heat sink exchanger input temperature, while on the bottom display the Heat sink
exchanger output temperature is shown for circuit 1 if there is 1 circuit. If instead there are two circuits, the average of the two
temperatures output from the exchangers is shown (if one of the two probes is in alarm, the value of the one not in alarm is shown).
6.4 StAt Menu
If you choose the Stat item from the general menu you enter the screen of certain main modes of the system (which you can browse
with the Left/Right keys) on the page of reference:
Table with examples of system modes viewable from Page 1
Page of reference Mode shown System mode
Page 1 Unit Indicates the mode the machine is operating in (OFF, ChIL, pdC, dEFr, dRIp,
F-C)
Page 1 ModE Indicates the machine operating mode (ChIL, pdC)
Page 1 tdF1 Accumulation of the wait time for a defrost circuit 1
Page 1 dFr1 Duration time of defrost circuit 1
Page 1 tdF2 Accumulation of the wait time for a defrost circuit 2
Page 1 dFr2 Duration time of defrost circuit 2
Page 1 SEtC Current setpoint summer operation
Page 1 SEtH Current setpoint winter operation
Page 1 rEGP Main regulation probe
Page 1 PREq Power requested [%]
Page 1 PSup Power supplied [%]
Table with examples system modes viewable from Page 2
Page of reference Mode viewed System mode
Page 2 CMP1, CMP2 .. CMP6 Compressor mode (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2 FAn1, FAn 2 Fan mode (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2 InF1,InF2 Speed of the condensation fans [%]
Page 2 PMP1, PMP2 Pump mode (dIS, OFF, On, ALAr, MAnU)
Page 2 PMS1, PMS2 Source pump mode (dIS, OFF, On, ALAr, MAnU)
Page 2 F-C Free-cooling activation state
Page 2 vF-C Free-cooling valve
Page 2 FF-C Free-cooling regulation
Page 2 vpC1 C1 parcelling valve mode for free cooling
Page 2 vpC2 C2 parcelling valve mode for free cooling