EasyManuals Logo
Home>Evco>Controller>c-pro 3 nano CHIL

Evco c-pro 3 nano CHIL User Manual

Evco c-pro 3 nano CHIL
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 71 of 90
PC51 = Pressure parcelling setpoint at low temperatures
PC52 = Pressure parcelling differential at low temperatures
PC53 = Low external temperature threshold
PC54 = Refrigerated water high temperature threshold
PC55 = Parcelling delay from low pressure alarm.
Depending on the number of compressors configured, the percentage of power limitation is calculated based on this parameter:
PC32 = Power limitation for winter operation
To enable this control, the external air temperature probe must be enabled
This control can be enabled only in winter operating mode (heat pump).
8.19.6 Operating limit management (heat pump)
When the external temperature drops to particularly low levels, it might no longer be cheap or sufficient to heat using the heat pump.
The Limit setpoint PC17 on the external temperature is used to disable the heat pump. Reactivation occurs when the external
temperature exceeds the limit setpoint plus a configurable Limit differential PC72.
T
aria
est.
Pressione
Soglia
Im
Imp+Diff
LPLT
Allarme
meno di 15 minuti
T
acqua
Soglia
Limit setpoint PC71
OFF
ON
Ext. T
Diff. PC72

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco c-pro 3 nano CHIL and is the answer not in the manual?

Evco c-pro 3 nano CHIL Specifications

General IconGeneral
BrandEvco
Modelc-pro 3 nano CHIL
CategoryController
LanguageEnglish

Related product manuals