• PC51 = Pressure parcelling setpoint at low temperatures
• PC52 = Pressure parcelling differential at low temperatures
• PC53 = Low external temperature threshold
• PC54 = Refrigerated water high temperature threshold
• PC55 = Parcelling delay from low pressure alarm.
Depending on the number of compressors configured, the percentage of power limitation is calculated based on this parameter:
• PC32 = Power limitation for winter operation
To enable this control, the external air temperature probe must be enabled
This control can be enabled only in winter operating mode (heat pump).
8.19.6 Operating limit management (heat pump)
When the external temperature drops to particularly low levels, it might no longer be cheap or sufficient to heat using the heat pump.
The Limit setpoint PC17 on the external temperature is used to disable the heat pump. Reactivation occurs when the external
temperature exceeds the limit setpoint plus a configurable Limit differential PC72.
est.
Pressione
Soglia
Im
Imp+Diff
LPLT
Allarme
meno di 15 minuti
Limit setpoint PC71
OFF
ON
Ext. T
Diff. PC72