Model Maximum
Operating
Temperatu
re 30°C
(86°F)
Maximum
Operating
Temperatu
re 35°C
(95°F)
(ASHRAE
CLASS A2
Compliant
)
Maximum
Operating
Temperature
40°C (104°F)
(ASHRAE
CLASS A3
Compliant)
Maximum
Operating
Temperature 45°C
(113°F) (ASHRAE
CLASS A4
Compliant)
NOTE
l If one fan fails, the highest operating temperature of the server is 5°C (9°F) lower than that in
normal cases.
l When GPUs are used, the failure of one fan may result in performance deterioration.
l If three P4 GPU cards or fewer are configured, the maximum operating temperature is 35°C
(95°F). If four P4 GPU cards or more are configured, the maximum working temperature is
30°C (86°F).
l Humidity
Operating humidity: 8% RH to 90% RH (non-condensing)
Storage humidity: 5% to 95% RH (non-condensing)
Humidity change rate: < 20% RH/h
l Air volume
204 CFM
l Altitude
≤3050 m (10006.44 ft). According to the ASHRAE standards of 2015, for altitudes
above 950 m (3116.79 ft), the highest operating temperature decreases by 1°C
(1.8°F) for every increase of:
n 300 m (984.24 ft) in altitude when the server configuration complies with
Class A2 standards.
n 175 m (575.14 ft) in altitude when the server configuration complies with
Class A3 standards.
n 125 m (410.10 ft) in altitude when the server configuration complies with
Class A4 standards.
HDDs are not supported when the altitude is higher than 3000 m (9842.4 ft).
l Corrosive gaseous contaminant
Copper corrosion rate test requirements: The corrosion product thickness growth
rate is lower than 300 Å/month (meeting level G1 requirements of the ANSI/
ISA-71.04-2013 standard on gaseous corrosion).
Silver corrosion rate test requirements: The corrosion product thickness growth rate
is lower than 200 Å/month.
l Particle contaminant
The equipment room environment meets the requirements of ISO 14664-1 Class 8.
You are advised to hire a professional organization to monitor particle contaminants
in the equipment room.
The equipment room is free from explosive, conductive, magnetic conductive, and
corrosive dust.
2288H V5 Server
User Guide
13 Product Specifications
Issue 04 (2018-09-04) Copyright © Huawei Technologies Co., Ltd. 255

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei 2288H V5 and is the answer not in the manual?

Huawei 2288H V5 Specifications

General IconGeneral
Form Factor2U rack server
ProcessorIntel Xeon Scalable processors
Max Processors2
Memory24 DDR4 DIMM slots
StorageSupports 25 x 2.5-inch drives
RAID SupportRAID levels 0, 1, 5, 6, 10, 50, 60
Network2 x GE ports
Expansion SlotsMultiple PCIe slots
Power Supply800W/1200W
Operating System SupportWindows Server, Red Hat Enterprise Linux, SUSE Linux Enterprise Server, VMware