Figure 4-25 Connecting cables to a DC PSU
Step 3 Connect the other end of each cable to the corresponding PDU by observing the power cable
connection rules.
Step 4 Bind the power cable to the cable trough using cable ties.
----End
4.5.9 Verifying Cable Connections
CAUTION
Before verifying cable connections, check that the power is cut off. Otherwise, any incorrect
connection or loose connection may cause human injury or device damage.
Check cable connections against Table 4-3.
Table 4-3 Cable connection checklist
Item
Description
Power cable Power cables are correctly connected to the rear of the chassis.
Network cable Network cables are connected correctly to the management port or
service ports on the rear panel of the chassis.
Ground cable The 2288H V5 server does not provide a separate ground port.
l In an AC or HVDC environment, the power cables of AC PSUs are
grounded. Ensure that the power cables are in good contact.
l In a DC environment, the ground terminals of DC PSUs are
grounded. Ensure that the ground cables are in good contact.