Document Name How to Obtain
Business Continuity and Disaster Recovery Solution
V200R001CXX User Guide (Active-Active Mode)
NOTE
This document uses product
versions in Table 3-3 as
examples. If the onsite product
versions are different from
those in the document, Log in
to http://
support.huawei.com/
enterprise/, and obtain the
Version Mapping specific to
the product versions at your
site and complete the
configuration.
HUAWEI Rack Server Product Documentation
3.2.2 Quick checklist for the installation environment
To implement a correct and smooth device installation, ensure that the installation
environment meets requirements before installing storage devices.
Table 3-4 lists the check items and requirements on the installation environment.
Table 3-4 Quick checklist for the installation environment
No.
Item Requirement
1 Site selection The site of the equipment room must be free of: high or low
temperature, heavy dust, harmful gas, inflammable or
explosive materials, electromagnetic interference (nearby
large-sized radar station, broadcast transmitting station, or
transformer station), unstable electric voltage, and large
vibration or strong noise. Therefore, during the engineering
design, you need to consider hydrology, geography,
earthquake, electric power, and transportation conditions
according to the technical requirements for communication
network planning and communication devices.
2 Civil construction The size of the equipment room must be sufficient for product
installation and capacity expansion. The floor can meet the
requirements for the bearing weight. The cable slot, cable
ladder, and cable holes are complete or ready. The decoration
is complete.
3 Operating
ambient
temperature
l When the altitude is lower than 1800 m (5904 feet), the
room temperature of controller enclosures and disk
enclosures must be kept within 5°C to 40°C (41°F to
104°F), and that of high-density disk enclosures must be
kept within 5°C to 35°C (41°F to 95°F).
l When the altitude ranges between 1800 m (5904 feet) and
3000 m (9840 feet), the room temperature must be kept
within 5°C to 30°C (41°F to 86°F).
OceanStor V3 Series
HyperMetro Feature Guide for File
3 Installation
Issue 05 (2018-01-30) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40