6. Description of Parameters
- 200 -
6
Function Code Parameter Name Setting Range Default
F8-49
Wakeup frequency Hibernating frequency (F8-51) to max.
frequency (F0-10)
0.00 Hz
F8-50
Wakeup delay time 0.0s to 6500.0s 0.0s
F8-51
Hibernating frequency 0.00 Hz to wakeup frequency (F8-49) 0.00 Hz
F8-52
Hibernating delay time 0.0s to 6500.0s 0.0s
During drive running, when frequency reference is equal to or smaller than F8-51, the AC drive
enters hibernating state after delay set in F8-52.
In hibernating state, when frequency reference is equal to or larger than F8-49, the AC drive
wakes up after delay set in F8-50.
When frequency reference setting channel is PID reference, whether to perform PID operation
in hibernating state is determined by FA-28 (Selection of PID operation at stop).
6.11.14 Running Time Threshold This Time
Function Code Parameter Name Setting Range Default
F8-53
Running time threshold this time 0.0 to 6500.0 min 0.0 min
If running time this time reaches the value set in this parameter, digital output terminal set for
function 40 becomes on, indicating that the running time this time is reached. It is effective
only for drive running this time. The previous running time is not added.
6.11.15 Output Power correction
Function Code Parameter Name Setting Range Default
F8-54
Output power correction
coefcient
0.00% to 200.0% 100.0%
This function parameter sets output power correction coefcient. When output power (U0-05)
is not equal to expected value, perform linear correction via this parameter.
6.11.16 Deceleration Time for Emergency Stop
Function Code Parameter Name Setting Range Default
F8-55
Deceleration time for
emergency stop
0 to 6553.5 Model
dependent
When the system is in emergency status, the AC drive decelerates based on the setting of F8-
55 (deceleration time for emergency stop). If F8-55 = 0 in V/F control, the AC drive decelerates
based on the setting of F0-19 (Acceleration/Deceleration time unit).