EasyManuals Logo
Home>Inovance>Inverter>MD500 Series

Inovance MD500 Series User Manual

Inovance MD500 Series
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
3. Electrical Installation
- 32 -
3
Cable Dimensions and Tightening Torque
Note
Data and models recommended in this section are for reference only.
The user selected cable diameter must not be larger than the terminal
width in the following gures.
Selection of IEC cables is based on:
Standards EN 60204-1 and IEC 60364-5-52
PVC insulation
40°C ambient temperature and 70°C surface temperature
Symmetrical cable with copper mesh shield
A maximum of 9 cables are allowed in a
cable tray.
For North America, the recommended cables in the preceding table must
be copper wires rated 600 V, 75°C.
Figure 3-1 Terminal dimensions of MD500T18.5GB/22GB-INT
136
16
15 17
16
15
M6 combination screw
Table 3-2 Recommended cable dimensions and tightening torque of MD500T18.5GB/22GB-INT
AC Drive Model Rated
Input
Current
(A)
Power
Input/Output
Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque
(N·m)
Screw
Spec.
MD500T18.5GB-INT 49.5 3 x 10 mm
2
3 x 6 AWG
8-6 10 mm
2
8 AWG
8-6 4.0 M6
MD500T22GB-INT 59 3 x 16 mm
2
3 x 4 AWG
14-6 16 mm
2
8 AWG
8-6 4.0 M6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD500 Series and is the answer not in the manual?

Inovance MD500 Series Specifications

General IconGeneral
BrandInovance
ModelMD500 Series
CategoryInverter
LanguageEnglish

Related product manuals