VECTOR 8 GENSET FVAE2885X*A100 MAINTENANCE PLAN
PRIME POWER
Prime Power is the maximum power available at variabl e loads for an unlimited number of hours. The average power available
during a 24 hour operating period should not exceed 80% of the prime power between the recommended servicing intervals in
standard environmental conditions.
An overload of 10% for 1 hour for every 12 hours of operation.
STAND-BY POWER
This is the maximum power available for a period of 500 hours/year with an average load factor of 90% of the stand-by power.
No type of overload is permitted for this usage.
CONTINUOUS POWER
Contact the Iveco Motors sales organization.
SECTION 3 - INDUSTRIAL APPLICATION 81
VECTOR 8 ENGINES
Print P2D32V001E Base - April 2006
Continuous / Prime Stand-By
Periodic Checks 100 h 1month
Hourly intervals
h
Time intervals
Hourly intervals
h
Time intervals
First level service 1000 1year 500 1year
Second level service 5000 2years 1000 2years
General overhaul 25000 10 years 2000 10 years
For special applications (heavy operating conditions, T
ambient
>40°C) the following reduction in these intervals is required:
Periodic checks
0%
First level service 0%
Second level service - 40%
General overhaul - 40%
LIST OF OPERATIONS
PERIODIC CHECKS
Check oil level/top up (Urania Turbo LD)
Check coolant level/top up
Check whether air/oil/diesel filter blocked warning lights are on (if wired)
Check water in diesel prefilter warning light