Technical data
Standards and operang condions
Conformies and approvals
Conformity
CE
2014/35/EU Low-Voltage Direcve
2014/30/EU EMC Direcve (reference: CE-typical drive system)
EAC
TR CU 004/2011 Eurasian conformity: Safety of low voltage equipment
TR CU 020/2011
Eurasian conformity: Electromagnec compability of
technical means
RoHS 2011/65/EU
Restricons on the use of certain hazardous substances in
electrical and electronic devices
Approval
UL UL 61800-5-1
for USA and Canada (requirements of the CSA 22.2 No.
274)
File No. E132659
Protecon of persons and device protecon
Degree of protecon
IP31
IP66
EN 60529
Informaon applies for completely and correctly installed
device.
NEMA Type 1
NEMA Type 4X outdoor
NEMA 250
UL Type 1
UL Type 4X outdoor
UL 50
UL 50E
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m amsl
Overvoltage category II EN 61800-5-1 over 2000 m amsl
Isolaon of control circuits
Safe mains isolaon via double/reinforced
insulaon
EN 61800-5-1
Protecve measures against
Short circuit
Earth fault Earth-fault protected depending on operang status
Overtemperature of motor PTC or thermal contact, I²xt monitoring
Overvoltage
Motor stalling
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Please observe regulaons and safety instrucons!
Inrush current
≤ 3 x rated mains current
EMC data
Operaon on public supply systems
Take measures to limit the expected radio
interference:
The machine or system manufacturer is responsible for
compliance with the requirements for the machine/system!
< 1 kW: With mains choke
EN 61000-3-2
> 1 kW for mains current ≤ 16 A: Without
addional measures
Mains current > 16 A: With mains choke
or mains lter, with dimensioning for
rated power.
EN 61000-3-12
Noise emission
Category C1 EN 61800-3 See rated data
Category C2 EN 61800-3 See rated data
Category C3 EN 61800-3 See rated data
Noise immunity
Fullls requirements according to EN 61800-3
Technical data
EMC data
102

Table of Contents

Other manuals for Lenze i550 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i550 Series and is the answer not in the manual?

Lenze i550 Series Specifications

General IconGeneral
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Overload Capacity150% for 60 seconds
Control TypeVector control
Communication InterfacesCANopen, Modbus, Ethernet, PROFIBUS, PROFINET
SafetySTO (Safe Torque Off)
Frequency Range0 Hz
Cooling MethodAir cooling
Storage Temperature Range-25°C to +70°C
Input Voltage Range3-phase 380...480 V AC -15%/+10%