Electrical installaon
Important notes
DANGER!
Electrical voltage
Possible consequences: Death or severe injuries
Any work on the inverter must only be carried out in the deenergised state.
Inverter up to 45 kW: Aer switching o the mains voltage, wait for at least 3 min before you start
working.
Inverter from 55 kW onwards: Aer switching o the mains voltage, wait for at least 10 min before you
start working.
DANGER!
Dangerous electrical voltage
The leakage current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an error.
Implement the measures requested in EN 61800−5−1 or EN 60204−1. Especially:
Fixed installaon
The PE connecon must comply with the standards (PE conductor diameter ≥ 10 mm
2
or use a double PE
conductor)
Electrical installaon
76

Table of Contents

Other manuals for Lenze i550 Series

Questions and Answers:

Lenze i550 Series Specifications

General IconGeneral
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Overload Capacity150% for 60 seconds
Control TypeVector control
Communication InterfacesCANopen, Modbus, Ethernet, PROFIBUS, PROFINET
SafetySTO (Safe Torque Off)
Frequency Range0 Hz
Cooling MethodAir cooling
Storage Temperature Range-25°C to +70°C
Input Voltage Range3-phase 380...480 V AC -15%/+10%