Connecon according to UL
WARNING!
▶
UL marking
▶
The integral solid state short circuit protecon included in the inverter does not provide branch circuit
protecon. Branch circuit protecon must be provided in accordance with the Naonal Electrical Code /
Canadian Electrical Code and any addional local codes.
▶
Marquage UL
▶
La protecon staque intégrée contre les courts-circuits n’ore pas la même protecon que le disposif
de protecon du circuit de dérivaon. Un tel disposif doit être fourni, conformément au Naonal
Electrical Code / Canadian Electrical Code et aux autres disposions applicables au niveau local.
NOTICE
▶
UL marking
▶
The opening of the Branch Circuit Protecve Device may be an indicaon that a fault has been
interrupted. To reduce the risk of re or electric shock, current-carring parts and other components of the
controller should be examined and replaced if damaged. If burnout of the current element of an overload
relay occurs, the complete overload relay must be replaced.
▶
Marquage UL
▶
Le déclenchement du disposif de protecon du circuit de dérivaon peut être dû à une coupure qui
résulte d'un courant de défault. Pour limiter le risque d'incendie ou de choc électrique, examiner les
pièces porteuses de courant et les autres éléments du contrôleur et les remplacer s'ils sont endommagés.
En cas de grillage de l'élément traversé par le courant dans un relais de surcharge, le relais tout ener doit
être remplacé.
NOTICE
▶
UL marking
▶
Internal overload protecon rated for 125 % of the rated FLA.
▶
Marquage UL
▶
Protecon contre les surcharges conçue pour se déclencher à 125 % de l'intensité assignée à pleine
charge.
WARNING!
▶
UL marking
▶
Use 75°C copper wire only, except for control circuits.
▶
Marquage UL
▶
Uliser exclusivement des conducteurs en cuivre 75 °C, sauf pour la pare commande.
Electrical installaon
Connecon according to UL
78