Operating 15088:J 10/22/99 2-3
This chapter refers to CMX Control Modules and MMX Monitor Modules. If XP or XP5 Series Transponders
are used, unless otherwise stated, the following substitutions may be made:
• MMX Monitor Modules can be substituted with XPM or XP5-M circuits.
• CMX Control Modules configured as Form-C contacts (tabs broken), can be substituted with XPR
circuits or XP5-C circuits (in relay mode).
• CMX Control Modules not configured as Form-C contacts can be substituted with XPC circuits or
XP5-C circuits (in NAC/telephone mode).
NOTE
See warning regarding XP Transponder operation at the beginning of Chapter Three, Section Three. For
more information, refer to the XP Series Transponder System Manual.
About the passwords
The AM2020/AFP1010 functions in one of three levels—Operational Level, Level One, and Level Two. In
Operational mode, the operator may perform the following keypad or menu-displayed functions:
• Acknowledge alarms, troubles, and restorations (clears)
• View acknowledged alarms, troubles, and restorations
• Silence the sounding of fire alarm notification appliances
• Reset the AM2020/AFP1010 System
• Test all intelligent addressable detectors in the system
• Test the panel's LED indicators, Liquid Crystal Display (LCD), terminal and printer
• Read the status of the entire AM2020/AFP1010 system, including the addressable devices
• Print out a report on the status of the system or access the history buffer
Access to keypad or menu levels one and two require entry of specific passwords. These levels allow an
authorized programmer to initialize or alter the programming of the AM2020/AFP1010. Level One and Level Two
entry requirements are defined as follows:
Alter Status Level One password required.
Programming Level Two password required.
If the main operator of the system requires access to a function which is password protected, contact the
distributor who installed the system for the required password(s). For more information on programming or altering
the status of the AM2020/AFP1010, refer to Chapter Three of this manual.
Whenever the operator selects a menu, the AM2020/AFP1010 begins a one-minute timer. If no key is pressed
during this minute, the function selected will be aborted and control will return to the state the panel was in prior to
selection of that menu.
NOTE
Unacknowledged points must be acknowledged prior to being reprogrammed. Any new trouble or alarm
reports reviewed during programming may disrupt the programming process. Do not change the
program parameters of any addressable point that is in alarm or trouble.
About the software
Depending on the particular release of software in your system, some menu functions and system features may
not be operable. If you attempt to execute a function not operable, the panel will respond with the message
"FUNCTION NOT ENABLED."
To the right are general terms and
their associated specific part numbers
as referenced in this manual:
MRET
TRAP
rebmuN
NRP5-NRP,4-NRP
TRC2-TRC
XMM
1-XMM
101-XMM
2-XMM
XMC2-XMCro1-XMC