1-85
Installation 15088: J 10/22/99
EIA-485 Reference
Earth Ground
EIA-485 (+)
EIA-485 (-)
EIA-485 (+)
EIA-485 (-)
EIA-232 Reference
Transmit to Printer
EIA-232 Reference
Receive from Printer
EIA-232 Reference
Transmit to AUX Printer
EIA-232 Reference
Ready/Busy from Keltron Printer
EIA-232 Reference
Transmit to CRT
EIA-232 Reference
Receive from CRT
EIA-232 Reference
Transmit to AUX Monitor
EIA-232 Reference
CTS from AUX Monitor
Figure 5.1-3 SIB-NET/SIB-2048A Terminal Designations
P3 Connections
Terminals 1-4: Provide wiring for one PRN printer to this
unsupervised circuit.
Terminals 5-8: Provide connection to the Keltron VS4095/
5 printer or any UL EDP-listed printer. Connection is not
supervised. EDP listed printers serve in an ancillary ca-
pacity only.
Terminals 9-12: Provide connection for 1–25 CRTs to this
supervised circuit.
Terminals 13-16: Provide connection to UL EDP-listed
display monitors. Devices are not supervised and serve in
an ancillary capacity only.
To ICA-4L
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals