3-44
Programming 15088:J 10/22/99
Select Alter Status
Menu Option 1-7
1 = DIS
(enable/disable of devices or
software zone)
2 = CTL
(manually turn on/off a
control module)
3 = DSEN
(alter sensitivity of any
addressable detector)
4 = TIME
(set the panel time/date
clock)
5 = DIAG
(perform system
diagnostics)
Press
ALTER STATUS
key
Enter Level 1
Password
Valid
Password?
Yes
No Error Message
6 = WALK
(specify LIBs for Walk Test,
and Walk Test reports)
7 = GZON
(Group Zone disable or
enable)
see Section 2.1
see Section 2.2
see Section 2.3
see Section 2.4
see Section 2.5
see Section 2.6
see Section 2.7
Figure 2-1 Alter Status Menu Flow Chart
Section 2.1 Disable Point C |X1X
1=DIS
Option 1 from the Alter Status Menu allows the programmer to disable and subsequently re-enable individual
devices or zones. When a device is disabled, it is no longer polled by the AM2020/AFP1010.
The following example illustrates disabling monitor module 4 on SLC Loop 1.
NOTE
The programmer should NEVER disable a point that is in alarm.
The programmer should never turn on (using option 2 of the Alter Status Menu) or program a disabled point.
Telephone (TELE) and remote page (PAGE) Type IDs can not be disabled.
PRESS@1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK,7=GZON@@@@@@@@@@@@@@@@@@:@1
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@CHANGE@(BCKSPC@TO@ABORT):@L1M4
DO@YOU@WANT@THIS@POINT@DISABLED?@(Y=YES,N=NO)@@@@@@@@@@@@@@@@@@@@@@@@@ :@Y
*
*
Note: Disable does not affect annunciator points.