Programming 15088:J 10/22/99
3-55
Group 5:
Output Modules
Display Label
CMX FORM C
CMX CONTROL
CONTROL
FORM C RELAY
FORMC MANUAL
SPEAKER
Type ID
CMXC
CMXS
CON
FORC
FRCM
SPKR
Group 6:
Supervisory/Security Modules
Note: Each Type ID listed above is prompted for Signal Silence during programming. If the silence option has been
programmed for these addressable devices, they can be turned off using the Control OFF function under the Alter Status
Menu or by pushing the appropriate annunciator point switch. Of the above Type IDs, only CON, FORC, and SPKR can
be silenced by pressing the Signal Silence button, initiating a partial signal silence. If the Software Type ID requires Form-
C relay function, the two tabs on the CMX must be broken. Otherwise, the tabs must not be broken.
Type of Device
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an
XP5-C (in relay mode).
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode)
configured as a Notification Appliance Circuit.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode)
configured as a Notification Appliance Circuit.
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an
XP5-C (in relay mode)
CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an
XP5-C (in relay mode). This device is not deactivated when a system reset
occurs. This module can be used for some fan control applications and can
be mapped only to an AFCM annunciator point.
CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode)
configured as a speaker circuit.
Type ID
SACM
SARM
SEQM
SPSU
SSYM
SUPR
Display Label
ACCESS MONTR
AREA MONITOR
EQUIP MONITR
SPRNKLR MNTR
SYSTEM MONTR
SPRVSRY MNTR
Type of Device
MMX Monitor Module or an XP5-M circuit used to monitor a security device.
This module will be activated by an open or a short condition. Activation of a
module with this Software Type ID will not initiate a security alarm condition:
• Security Alarm LED will not illuminate.
• Does not activate trouble status line count on a CRT.
• No effect on modules programmed as TPND (trouble
pending) or GPND (general event pending).
• Trouble, clear trouble or acknowledgments are not reported
for this type.
MMX Monitor Module or an XP5-M circuit used to monitor a security device.
This module will be activated by either an open or a short condition and
produces a SECURITY ALARM message in the display.
MMX Monitor Module or an XP5-M circuit that functions identically to Type
ID SACM.
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit dedicated to
a normally open sprinkler supervisory switch. Activation of a module with
Software Type ID SPSU will generate a trouble condition (produces a
SPRNKLR TROUBLE message) not an alarm. The option of Tracking
(troubles self-restore) is automatically selected for this software type.
MMX Monitor Module or an XP5-M circuit used to monitor a security device.
This module will be activated by either an open or a short condition and
produces a SECURITY TAMPER message in the display.
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit dedicated to
a normally open supervisory switch. Activation of a module with Software
Type ID SUPR will generate a trouble condition (produces a SUPRVSRY
SIGNAL message) not an alarm.