4-7
Security 15088:J 10/22/99
The following figures illustrate the minimum system requirements for various configurations of the AM2020/
AFP1010 and associated peripherals.
Refer to Table 1.1-1 in the introduction to this chapter for monitor and control module information. Refer to the
XP5 Series Transponder Manual listed in the Related Documentation Chart of this manual for connection
information for the XP5 modules. Refer as well to the Product Installation Documents 15984 (RKS-S Remote
Keyswitch) and 15456 (STS-1 Security Tamper Switch) for connection information on these devices.
Refer to the Glossary section of this manual for descriptions of the terms used in this section.
Security System Diagrams and Programming Keys
Figure 1.3-1 Simplest Security System
The following system requirements are illustrated in Figure 1.3-1. See Table 1.1-1 the introduction to this section
for other monitor module options.
• One AM2020/AFP1010 Control Panel
• One Security Supervisory Protected Area
• One Protected Premises
• One MMX-1 or MMX-101 Monitor Module, Security Devices (minimum security equipment).
Area1.cdr
Key
Motion Detector
MM Security Area Monitor
1
Signaling Line Circuit
(SLC)
AM2020/AFP1010
Central Station
AREA 1
(Perimeter)
TENANT A
47K End-of-Line Resistor (A-2143-00)
Normally open security
switch (listed)
Normally closed security
switch (listed)
MMX-1 or MMX-101
Security Area Monitor
(See Fig 1.3-7 for MMX-101 wiring
polarity)
SLC to LIB at
Central Station
Contact Switch
Pull Station
Smoke Detector
Programming Key for Figure 1.3-1
MM Security Area Monitor:
Address: LXXMYY (Installer specified).
Type ID: SARM
Control-By-Event: ( )
Custom Label: Installer Specified (describe location of module).
Tracking: Yes - Results in required acknowledgment at Central Station for every unsecured state.
Restoral is automatic.
No - Results in required acknowledgment at Central Station for first unsecured state only (until
reset at Central Station - short condition only).
Annunciator: No (not required).
Yes (if annunciator mapping desired)
Annunciator Point
Mapping (Optional): AxxPyy
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals