4-14
Security 15088:J 10/22/99
Group Interface:
A: CM programming:
Address: LXXMYY (Installer specified).
Type ID: CMXC
Control-By-Event: (Zaj*)
Custom Label: Security Group Output
Signal Silence: No
Walk Test: Yes/No (Installer Specified).
Annunciator: No (Not required).
MM Security Access Monitor:
Address: LXXMYY (Installer specified).
Type ID: SACM
Control-By-Event: (Zaa*)
Custom Label: Installer Option (describe specific
location of module).
Tracking: Yes—Each unsecured state will
be printed when the print option is
enabled.
No—The first unsecured state will
be printed when the print option is
enabled (restorals will not print un-
til reset at Central Station - short
condition only).
Annunciator: Yes
Annunciator Point: AXXP4
B: MM programming:
Address: LXXMYY (Installer specified).
Type ID: SARM
Control-By-Event: ( )
Custom Label: Installer Specified.
Tracking: Yes—Results in required a c -
knowledgment at Central Station
for every unsecured state. Resto-
ral is automatic.
No—Results in required acknowl-
edgment at Central Station for first
unsecured state only (until reset at
Central Station - short condition
only).
Annunciator: No (Not required).
MM = CM
Zone Programming
1. Zone Boundary: Must be less than Zad* and greater than or equal to Zac*.
5. Zone Activated When Any Instant Module Is Vi-
olated and the System Is Armed
Zone: Zad*
Type ID: RZON
Control-By-Event: AND(Zaa* Zab*)
Custom Label: Installer Specified.
Annunciator: No (Not required).
6. Zone Active for 30 Sec., 30 Sec. After Opening
Entry/Exit Door (Not Dependent on Door Clo-
sure)
Zone: Zae*
Type ID: RZON
Control-By-Event: SDEL(00.00.30 00.00.30 (Zac*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
7. Zone Active 1 Min. After Entry/Exit Door Is
Opened and Left Open
Zone: Zaf*
Type ID: RZON
Control-By-Event: DEL(00.01.00 (Zac*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
2. Zone to Which All Instant Security Modules
Are Mapped
Zone: Zaa*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Instant Group
Annunciator: No
3. Zone Activated Upon Arming System
Zone: Zab*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Arming Zone
Annunciator: Yes
Annunciator Point: AXXP2
4. Zone Activated When Entry/Exit Door Is Open
Zone: Zac*
Type ID: FZON
Control-By-Event: ( )
Custom Label: Tenant A Entry/Exit
Annunciator: No (Not required).
ACM-16AT/-32A Annunciator:
Annun. Pt. Type ID
AXXP1 AMON
AXXP2 AZON
AXXP3 AMON
AXXP4 AMON
Programming Key for Figure 1.3-6 (Cont)
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals