EasyManuals Logo
Home>Notifier>Fire Alarms>AFP1010

Notifier AFP1010 User Manual

Notifier AFP1010
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
Programming 15088:J 10/22/99
3-63
Duration
(optional)
Internal
Equation
Delay
DEL
Operator: For delayed operation, the DEL operator is used.
Equation: DEL(HH.MM.SS HH.MM.SS (Z1))
Example: L1M3 activates Forward Activating Zone 223 (Z223).
L1M2 CBE is: DEL(00.00.30 00.01.30 (Z223))
IF Z223 has been active for 30 seconds
THEN L1M2 will become active. L1M2 will stay active
for 1 minute and 30 seconds provided that Zone Z223
remains active.
Time line
0:00 0:30 1:00 1:30 2:00 2:30
+————+————+————+————+————+
Z223 L1M2 L1M2
active active inactive
NOTES
• The entire DEL equation consumes at least 11 bytes (including a 3-byte internal equation). The internal
equation can be a complex equation many bytes in size.
• If a delay of zero is entered (00.00.00), the equation will evaluate true as soon as the internal equation
evaluates true and will remain that way for the specified duration, unless the internal equation
becomes false.
• If no duration is specified, then the device will not be deactivated until a reset occurs or the internal
equation evaluates false.
Z223
L1M2
CMX
L1M3
(Z223)
DEL(00.00.30 00.01.30
(Z223))
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals