Programming 15088:J 10/22/99
3-39
Section 1.5 Remove  D }X5X
5=REMV
Option 5 from the Programming Menu allows the programmer to remove (from control panel memory) SLC
Loop devices, software-defined zones or annunciator points. The devices can still be installed in the system,
but the AM2020/AFP1010 will stop looking for these devices by not addressing them.
NOTES
Devices that are removed from the system's program will not function in any capacity until reinstalled
under Full Point Programming.
CAUTION - devices that have had their LEDs latched ON must be returned
to their normal state before removal (execute System Reset for detectors or control OFF for modules).
Unacknowledged points must be acknowledged prior to removal.
The programming example below illustrates the CRT screen prompts during removal of an SLC Loop device
(smoke detector 34 on SLC Loop 10).
PRESS@1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS@@@@@@@@@@@@@@@@@@:@5
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.@REMOVAL@(BCKSPC@TO@ABORT)@@@:@L10D34
Section 1.6 Password D }X6X
6=PSWD
Option 6 from the Programming Menu allows the programmer to change the Level One and Level Two
passwords for the AM2020/AFP1010.
NOTES
The AM2020/AFP1010s are shipped with initial Level One and Level Two passwords of 00000. As a
security measure, the control panel does not echo password digits to the DIA and CRT screen. Rather,
it displays an asterisk (*) for each digit entered. After entering five password digits, pressing ENTER
(on the DIA) or RETURN (on the CRT) places the new password into operation.
Acceptable characters for a password are the digits 0-9.
PRESS@1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS@@@@@@@@@@@@@@@@@@:@6
PRESS@1=LEVEL@ONE,2=LEVEL@TWO@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:@2
@@@@@ENTER@LEVEL@TWO@PASSWORD:@*****
A Forgotten Password?
If a Level One or Level Two password is incorrectly entered, the panel will respond by displaying a special
code word and prompt the programmer to reenter the password. If the password has been forgotten, record
this code word and contact NOTIFIER. After proper authentication, the original password can be determined
from deciphering the code word. An example of this code word follows:
@@@ENTER@LEVEL@ONE@PASSWORD:@*****
@@INVALID@PASSWORD:@@@@@@@7129406@@@@@@@@@REENTER@PASSWORD:
Section 1.7 Message D }X7X
7=MSG
Option 7 from the Programming Menu allows the programmer to change the 40-Character Custom User Label
for the system. Acceptable characters for the label include Letters A though Z, digits 0 through 9, periods (.),
dashes (-), and spaces.
PRESS@1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS@@@@@@@@@@@@@@@@@@:@7
ENTER@40@CHARACTER@CUSTOM@USER@LABEL@@:@NOTIFIER@@@@@@@@@@@@@@@@@@@@@@@@@@@
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals