Appendices 15088:J 10/22/99
A-5
Table A-2 (Continued)
Type of Circuit Devices/Ratings Circuit Ratings Connections
Municipal Box
Circuit
CMX Control Module or XP5-C
Transponder Module with an MBT-
1 Municipal Box Trip device and
an A77-716 power supervision
relay.
Local Energy Municipal Box connection. Supervised and power-
limited. (3.65 VDC nominal). (10 ohms max. loop resistance. Trip
current = 250 mA.
Refer to Supervising an Uninterruptable
Power Supply in the AM2020/AFP1010
Manual.
XP Transponder XPC-8 module
with an MBT-1 Municipal Box Trip
device.
Local Energy Municipal Box connection. Supervised and power-
limited. (3.65 VDC nominal). 10 ohms max. loop resistance. Trip
current = 250 mA.
Refer to Appendix A of the XP Series
Transponder Manual.
24 VDC
Notification
Appliance Circuit
A circuit or path
directly
connected to a
24 VDC
notification
appliance.
CMX Control Module fed from an
MPS-24A/MPS-24AE, MPS-
24B/MPS-24BE, APS-6R or other
24 VDC power supplies listed for
Fire Protective Signaling.
Operating voltage supplied dependent on the signal power source
employed. ELR=47K, 1/2 watt, Part #47K (N-ELR) in Canada. NFPA
Style Y or Style Z field wiring. Max Load is 2 amps Resistive @ 24
VDC. Most Notification Appliances are resistive. Certain
electromechanical devices exhibit inductive loading characteristics.
For these types of devices, derate the outputs to 1 amp @ 30 VDC
(0.6pf). Size wiring for no more than 1.2 volt drop at last device on
circuit. Supervised. Power limiting is a function of the power source.
NFPA Style Y Activated Polarity CMX
Terminal 6 (+), 7 (-).
NFPA Style Z Activated Polarity CMX
Terminals 6, 9 (+); 7,8 (-).
XP5-C Transponder Circuit fed
from an MPS-24A/MPS-24AE,
MPS-24B/MPS-24BE, APS-6R, or
other 24 VDC listed power supply.
Operating voltage supplied dependent on the signal power source
employed. ELR=47K, 1/2 watt, Part #47K (N-ELR) in Canada. NFPA
Style Y field wiring. Total current to all notification applicances cannot
exceed 3A(non-coded DC), 2A (DC). Most Notification Appliances
are resistive. Certain electromechanical devices exhibit inductive
loading characteristics. For these types of devices, derate the outputs
to 1 A, 24 VDC, inductive (L/R=2 ms) coded. 0.5A, 30 VDC,
inductive (L/R=5 ms) coded. Size wiring for no more than 1.2 volt
drop at last device on circuit. Supervised. Power limiting is a function
of the signaling power source.
NFPA Style Y Activated Polarity (5 circuits
on XP5-C)
TB1-TB5: B-, B+
XP Transponder XPC-8 module
fed from an MPS-24A/MPS-24AE,
MPS-24B/MPS-24BE, APS-6R or
other 24VDC listed power supply.
Operating voltage supplied dependent on the signal power source
employed. ELR=47K, 1/2 watt, Part #47K (N-ELR) in Canada. NFPA
Style Y and Style Z field wiring. Max Load is 2 amps Resistive @ 24
VDC. Most Notification Appliances are resistive. Certain
electromechanical devices exhibit inductive loading characteristics.
For these types of devices, derate the outputs to 1 amp @ 30 VDC
(0.6pf). Size wiring for no more than 1.2 volt drop at last device on
circuit. Supervised. Power limiting is a function of the power source.
NFPA Style Y Activated Polarity (8 zones
on XPC-8 P2): Term.1 (+),2(-); 3(+), 4(-);
5(+), 6(-); 7(+), 8(-); 9(+),10(-); 11(+),12(-);
13(+), 14 (-); 15(+), 16(-).
NFPA Style Z Activated Polarity (4 zones
on XPC-8 P2): Term. 1,3(+), 2,4 (-); 5,7 (+),
6,8 (-), 9,11 (+), 10,12 (-); 13,15 (+), 14,16
(-).
Speaker
Notification
Appliance
Circuits
CMX-1 Control Module fed from
an AA-30/AA-30E, AA-100/AA-
100E or AA-120/AA-120E.
Operating voltage dependent on amplifier employed. Max of 40 mA
total speaker leakage current due to coupling capacitors. 48 watts
max @ 25 VRMS max. ELR=47K, 1/2 watt, Part # A2143-20 (N-ELR
in Canada). Max. line resistance dependent upon wattage required at
each speaker. NFPA Style Y field wiring. Supervised. Power limiting
is a function of the signaling power source.
NFPA Style Y supervised polarity CMX
Terminals 7(+), 6(-).
CMX-2 Control Module fed from
an audio amplifier. Model A2143-
20 coupling capacitor (10uA
leakage max.) is required for
NFPA Style Z connection. Refer to
the CMX-2 installation instructions
for more details.
Operating voltage dependent on amplifier employed. 43.75 watts
max., up to 70.7 VRMS. Max of 40 uA total speaker leakage current
due to coupling capacitors. ELR=47K, 1/2 watt, Part # A2143-00 (N-
ELR in Canada). Max. line resistance dependent upon wattage
required at each speaker. NFPA Style Y and Z field wiring.
Supervised. Power limiting is a function of the signaling power
source.
NFPA Style Y supervised polarity: CMX
Terminals 7 (+), 6(-).
NFPA Style Z supervised polarity: CMX
Terminals 7,8 (+); 6,9 (-).
XP Transponder XPC-8 module
fed from an audio amplifier.
Operating voltage dependent on amplifier employed. 50 watts max @
25 Vrms, 70 watts@ 70.7 Vrms max. ELR=47K, 1/2 watt, Part # R-
47K (N-ELR in Canada). Max line resistance dependent upon
wattage required at each speaker. NFPA Style Y or Style Z field
wiring. Supervised. Power-limiting is a function of the signal source.
NFPA Style Y supervised polarity (8 zones
on XPC-8 P2):Term.1(-), 2(+); 3(-), 4(+);5(-
),6(+); 7(-), 8(+); 9(-), 10(+); 11(-), 12(+);
13(-), 14(+); 15 (-), 16(+).
NFPA Style Z supervised polarity (4 zones
on XPC-8 P2): Term. 1,3 (-),2,4,(+); 5,7 (-
),6,8(+); 9,11 (-), 10,12 (+);13,15 (-), 14,16
(+).
XP5-C Transponder circuit fed
from an audio amplifier.
Operating voltage dependent on amplifier employed. 75 watts max @
25 Volts, 64 watts max @ 70.7 Vrms max. ELR=47K, 1/2 watt, Part #
R-47K (N-ELR in Canada). Max line resistance dependent upon
wattage required at each speaker. NFPA Style Y field wiring.
Supervised. Power-limiting is a function of the signal source.
NFPA Style Y supervised polarity (5
circuits on XP5-C)
TB1 - TB5; B-, B+
Speaker Power
(High-level
Audio)
AA-30/AA-30E, AA-100/AA-100E
or AA-120/AA-120E Audio
Amplifier feeding signal to a CMX
Control Module, an XP
Transponder XPC-8 Module, or an
XP5-C transponder circuit. Use
only UL listed speakers rated for a
minimum 25 VRMS (30 watts max
with AA-30/AA-30E, 120 watts
max with AA-120/AA120E) or 70.7
VRMS min. when using the AA-
100/AA-100E. (100 watts max.).
25 Vrms audio amplifier output (70.7 Vrms for AA-100/AA-100E).
AA-30/AA-30E: 30 watts max. AA-120/AA-120E: 120 watts max.
AA-100/AA-100E 100 watts max.
Frequency response: 800 Hz to 2800 Hz. Two wire high level audio
circuit is not supervised. Four-wire high level audio circuit is
supervised. AA-30/AA-30E, AA-100/AA-100E and AA-120/AA-120E
are power-limited. Maximum wiring distance limited by wattage
required at each speaker.
AA-30/AA-30E, AA-100/AA-100E and AA-
120/AA-120E Connector P6 to XP5-C
(TB1-TB5), XPC-8 Connector P3: AA-
30/AA-30E Connector P6 (or P8.5 (-) and
P8.6(+)) to CMX Term 3(-) and 4(+). Wire
optional supervisory return loop from CMX
Term 3(-) and 4(-) to AA-30/AA-30E
Connector P7 or P8.2(-), P8.3(+) or AA-
120/AA-120E P8.2(-),P8.3(+). AA-
100/AA-100E: connnect 25 VRMS output
P7.3 and P7.4 to a transformer input P7.1
and P7.2 to obtain 70.7 VRMS output at
P8.7 and P8.8. Connection not
supervised.
www.PDF-Zoo.com