Appendices 15088:J 10/22/99
A-7
Table A-2 (Continued)
Type of Circuit Devices/Ratings Circuit Ratings Connections
LIB-200 SLC Loop
A circuit or path directly
over which multiple
signals are transmitted
and received.
LIB-200 Board: Employs intelligent
detectors and addressable modules -
SDX-551,SDX-551TH,SDX-751, FDX-
551,CPX-551,CPX-751,IPX-751,MMX--
1, MMX-2, MMX-101,XP5-M, XP5-C,
CMX-1, CMX-2, NBG-12LX, BGX-10L,
XPP-1, ISO-X.Ten SLC Loops max per
AM2020 system,4 per AFP1010.
When more than 100 Isolator
Modules/Isolator Bases are connected
to an SLC Loop, decrease the 198
address capacity by two addresses for
every isolator in excess of 100.
24 Volts DC nominal, 27.6 volts DC maximum.
Maximum length is 10,000 ft. (3048 m) per
channel (NFPA Style 4) or 10,000 ft. (3048 m)
total twisted-shielded pair length (NFPA Style 6
and 7). Maximum loop current is 200mA (short
circuit) or 100 mA (normal). Maximum loop
resistance is 40 ohms. Supervised and power-
limited.
NFPA Style 4: LIB-200
Channel A - Term. 1 (+), 3 (-);
Channel B - Term. 5 (+), 7 (-).
NFPA Style 6, 7: LIB-200
Term. 1, 5 (+); 3,7 (-).
LIB-200A or LIB-400
SLC Loop
A circuit or path directly
over which multiple
signals are transmitted
and received.
LIB-200A/LIB-400 Board: Employs 99
intelligent detectors and 99
addressable modules - SDX-551, SDX-
551TH, SDX-751, FDX-551, CPX-551,
CPX-751, IPX-751, MMX-1, MMX-2,
MMX-101, XP5-M, XP5-C, CMX-1,
CMX-2, NBG-12LX, BGX-10L, XPP-1,
ISO-X. Ten SLC Loops max per
AM2020 system, four per AFP1010.
When more than 100 Isolator
Modules/Isolator Bases are connected
to an SLC Loop, decrease the 198
address capacity by two addresses for
every isolator in excess of 100.
24 Volts DC nominal, 27.6 volts DC maximum.
Maximum length is 12,500 ft. (3810 m) per
channel (NFPA Style 4) or 12,500 ft. (3810 m)
total twisted pair length (NFPA Style 6 and 7).
Maximum loop current is 200mA (short circuit) or
100 mA (normal). Maximum loop resistance is
50 ohms. Supervised and power-limited.
NFPA Style 4: LIB-200A/LIB-
400
Channel A - Term. 1 (+), 3 (-);
Channel B - Term. 5 (+), 7 (-).
NFPA Style 6, 7: LIB-200A/LIB-
400
Term. 1, 5 (+); 3,7 (-).
NOTI•FIRE•NET™
SLC
A series of modules and
products which allow a
group of Fire Alarm
Control Panels (FACPs)
and other control
equipment to connect,
forming a true peer-to-
peer network
MIB-W: Media Interface Board used to
connect nodes with twisted-pair wire
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
Port A - TB1 - 1 and 2
Port B - TB1 - 3 and 4
MIB-F: Media Interface Board used to
connect nodes with fiber-optic cable
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
Port A - U1 (Tx), U5 (Rx)
Port B - U2 (Tx), U3 (Rx)
MIB-WF: Media Interface Board used
to connect from twisted-pair wire to fiber
or fiber to twisted-pair wire at any
network node.
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Port A - refer to the
NOTI•FIRE•NET manual, Document 50257 for
distance limits. Port B - Fiber Type: 62.5/125
micrometers, Wavelength: 820 nanometers,
Maximum Attenuation: 10 dB.
Port A (wire) - TB1 - 1 and 2
Port B (fiber) - U2 (Tx), U3 (Rx)
RPT-W: Repeater used to boost the
data signal between network nodes
supporting twisted-pair wire only.
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
Port A: TB1- 1 and 2
Port B: TB1- 3 and 4
RPT-F: Repeater used to boost the
data signal between network nodes
supportingh fiber-optic cable
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
Port A: U14 (Tx), U11 (RX)
Port B: U15 (Tx), U12 (RX)
RPT-WF: Repeater used to boost the
data signal between network nodes
supporting both twisted-pair wire and
fiber-optic cable
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Port A - refer to the
NOTI•FIRE•NET manual, Document 50257 for
distance limits. Port B - Fiber Type: 62.5/125
micrometers, Wavelength: 820 nanometers,
Maximum Attenuation: 10 dB.
Port A (wire) TB1- 1 and 2
Port B (fiber) U15 (Tx), U12
(RX)
NAM-232W: Network Adapter Module
functioning as an interface between the
AFP200 FACP and the NOTI•FIRE•NET
with twisted-pair wire
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
PortA: TB2 - 1 and 2
Port B: TB2 - 3 and 4
NAM232F: Network Adapter Module
functioning as an interface between the
AFP200 FACP and the NOTI•FIRE•NET
with fiber-optic cable
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
Port A: J2 (Tx), J1 (RX)
Port B: J4 (Tx), J3 (RX)
www.PDF-Zoo.com