363
Appendix B
Sample Programs
Obtaining Analog Input Conversion Values
This is a program for obtaining the Analog Input Unit’s input conversion values. Individual input values are
obtained by MOV(021) when their Disconnection Detection Flags are OFF.
Unit Settings
Program Example
Writing Analog Output Set Values
This is a program for writing the Analog Output Unit’s output set values.
Unit Settings
Item Setting contents Actual settings
Unit CS1W-AD081-V1 ---
Unit number #0 Unit number switch: 00
Operation mode Normal mode Back-panel DIP switch: All OFF
Input number Inputs 1 to 8 used D20000 = 00FF
Input signal range All input numbers, 1 to 5 V D20001 = AAAA
200900
MOV(021)
2001
D00000
200901
MOV(021)
2002
D00001
Conversion value
Conversion value
200907
MOV(021)
2008
D00007
Conversion value
Input 1 Disconnection Detection Flag
Input 2 Disconnection Detection Flag
Input 8 Disconnection Detection Flag
Item Setting contents Actual settings
Unit CS1W-DA08V ---
Unit number #0 Unit number switch: 00
Operation mode Normal mode Back-panel DIP switch: All OFF
Output number Output 1 used D20000 = 0001
Output signal range Output number 1, 0 to 10 V D20001 = 0001