58
Analog Input Functions and Operating Procedures Section 2-6
Response Time at 250-µs
Conversion Time/8,000
Resolution
Unit: ms
Symbols M: Number of input words used in DM Area
N: Average number of buffers set for the input number for which to find the
response time
Calculation Example The following example calculations are for a resolution of 8,000 with an appli-
cation using inputs 1 and 8, 64 averaging buffers set for input 1, and no aver-
aging set for input 8.
• Response time for input 1: t = {(64
− 2) x 2 + 10.5} x 1/4 = 34 (ms)
• Response time for input 1: t = 1 x (2 + 2) x 1/4 = 1 (ms)
2-6-4 Peak Value Hold Function
The peak value hold function holds the maximum digital conversion value for
every input (including mean value processing). This function can be used with
analog input. The following diagram shows how digital conversion values are
affected when the peak value hold function is used.
The peak value hold function can be set individually for each input number by
turning on the respective bits (00 to 07 for CS1W-AD081-V1, 00 to 03 for
CS1W-AD041-V1) in CIO word n.
MN
64 32 16 8 4 2 1
16 250.625 122.625 58.625 26.625 10.625 9 4.5
15 235.125 115.125 55.125 25.125 10.125 8.5 4.25
14 219.625 107.625 51.625 23.625 9.625 8 4
13 204.125 100.125 48.125 22.125 9.125 7.5 3.75
12 188.625 92.625 44.625 20.625 8.625 7 3.5
11 173.125 85.125 41.125 19.125 8.125 6.5 3.25
10 157.625 77.625 37.625 17.625 7.625 6 3
9 142.125 70.125 34.125 16.125 7.125 5.5 2.75
8 126.625 62.625 30.625 14.625 6.625 5 2.5
7 111.125 55.125 27.125 13.125 6.125 4.5 2.25
6 95.625 47.625 23.625 11.625 5.625 4 2
5 80.125 40.125 20.125 10.125 5.125 3.5 1.75
4 64.625 32.625 16.625 8.625 4.625 3 1.5
3 49.125 25.125 13.125 7.125 4.125 2.5 1.25
2 33.625 17.625 9.625 5.625 3.625 2 1
1 16.75 8.75 4.75 2.75 1.75 1.25 0.75
Peak value hold
Digital conversion value
t (Time)
Conversion value when
the peak value hold
function is used
Input 2
Input 1
Input 4
Input 3
Input 6
Input 5
Input 8
Input 7
Bit1514 131211 10 090807 06 05040302 0100
n = D20000 + unit number x 10
Word n
Input 10
Input 9
Input 12
Input 11
Input 14
Input 13
Input 16
Input 15