Operating Procedure Section 2-2
• The following diagram shows the conversion time/resolution setting.
(Refer to
2-6-2 Conversion Time/Resolution Setting.)
Note For CS1W-AD161, set D(m+19):D20119.
2. Restart the CPU Unit.
Creating Ladder Programs
The data that is converted from analog to digital and output to CIO words (n +
1) to (n+ 7) of the Special I/O Unit Area (CIO 2011 to CIO2017), is stored in
the specified addresses D00100 to D00106 as signed binary values 0000 to
0FA0 Hex.
15 14 13 12 11 10 09 08 07 06 05 01 0004 03 02
0 0 0 0 0 0 0 0
Bit
(0000 Hex)
m+18: D20118
(See note.)
Conversion Time/Resolution Setting
0000: 1-ms conversion time, 4,000 resolution
C100: 250-
µs conversion time, 8,000 resolution
Power turned ON again
(or Special I/O Unit Restart Bit is turned ON)
Peripheral port