64
Adjusting Offset and Gain Section 2-7
Wiring for Voltage Input
Wiring for Current Input
When using current input, short-circuit the input (+) terminal and the current
mode terminal.
3. Input the voltage or current so that the conversion value becomes 0000.
The following table shows the offset adjustment voltages and currents to
be input according to the input signal range.
Input signal range Input range Word (n+8) monitoring
value
0 to 10 V –0.5 to 0.5 V FF38 to 00C8 (4,000 res-
olution)
FE70 to 0190 (8,000 res-
olution)
–10 to 10 V –1.0 to 1.0 V
1 to 5 V 0.8 to 1.2 V
0 to 5 V –0.25 to 0.25 V
4 to 20 mA 3.2 to 4.8 mA
A1
A2
A3
+
–
Voltage input
In
ut 1
CS1W-AD041-V1/081-V1
Voltage n
+
−
Shield
Input n+
Current mode n
Input n−
AG
CS1W-AD161
A1
A2
A3
+
–
Current input
Input 1
For current input, check that the voltage/
current switch is ON.
CS1W-AD041-V1/081-V1
Current input n
+
−
Shield
Input n+
Current mode n
Input n−
AG
CS1W-AD161