EasyManuals Logo
Home>Omron>Touch terminals>NS - SETUP

Omron NS - SETUP User Manual

Omron NS - SETUP
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
3-8 Installing the Controller Link Interface Unit
3-45
z Indicators
Indicator Name Color status Meaning
RUN Operating Green Lit Normal operation.
Not lit A Board operating error (watchdog timer error) occurred.
ERC Communica-
tions error
Red Lit One of the following errors occurred.
• Communications error
• Same node address used twice (i.e., address duplica-
tion error)
• Hardware error
Not lit Normal operation
ERH EEPROM error Red Lit One of the following errors occurred.
• EEPROM error
• EEPROM data link table error
• EEPROM routing table error
• EEPROM network parameter error
Not lit No EEPROM error.
INS Network par-
ticipation
Yellow Lit The Board is participating in the network.
Not lit The Board is not participating in the network.
SD Send Yellow Lit Sending data.
Not lit Not sending data.
RD Receive Yellow Lit Receiving data.
Not lit Not receiving data.
LNK Data link Yellow Lit Participating in data link.
Flash-
ing
Error in data link table setting.
Not lit Not participating in data link or data link inactive.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NS - SETUP and is the answer not in the manual?

Omron NS - SETUP Specifications

General IconGeneral
BrandOmron
ModelNS - SETUP
CategoryTouch terminals
LanguageEnglish

Related product manuals